Central Water Chiller : Air-Cooled

Model: TI-40A

PRODUCT SPECIFICATIONS
  • Model: TI-40A (1)
  • Refrigerant Zones
  • Quantity : 2
  • Compressor
  • Quantity : 2
  • HP : 20
  • Type : Scroll
  • (2) Total Capacity : 40 Tons
  • Refrigerant
  • Type : R-410A
  • Process Pump
  • HP : 7.5
  • GPM : 96
  • PSI : 60
  • (3) Evaporator Pump
  • HP : 3
  • GPM : 96
  • Reservoir Capacity
  • Operating : 340 gal
  • Holding : 400 gal
  • Connection Sizes
  • To Process : 3"
  • From Process : 3"
  • Water Make-Up : 1"
  • Overflow : 4"
  • (5) Full Load Amperage
  • 230/3/60 : 170.0
  • 460/3/60 : 85.0
  • 575/3/60 : 68.0
  • Dimensions
  • Height : 82"
  • Width : 92"
  • Depth : 96"
  • Weight
  • (7) Shipping : 4,350 lbs
  • Operating : 8,710 lbs
  •  
  • Remote Air-Cooled Condenser
  • Quantity
  • Advantage Model : RCDZ-40-LK
  • Numbers of Units : 1
  • Capacity
  • R410A @ 1° TD : 30.2 MBTU/hr
  • R410A @ 20° TD : 41.6 tons
  • Fans
  • Quantity : 4
  • RPM : 1,140
  • Connections
  • Gas : 2@1-5/8"
  • Liquid : 2@1-5/8"
  • Full Load Amperage
  • 460/3/60 : 14.0
  • Construction
  • Tube Material : Copper
  • Fin Material : Aluminum
  • Fins Per Inch : 12
  • Coating : None
  • Dimensions
  • Height : 49.13"
  • Width : 88"
  • Depth : 127"
  • Weight
  • Weight : 1,340 lbs
  • Circuits Served
  • Maximum : 2
  • Reference #
  • Reference : LNH-D04-A029(12)
  • EC Reference : LNH-D04-A029(12)-AdvEng
  •  
  • Specification Notes:
  • 1. Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
  • 2. Tons capacity at 12,000 BTU/ton per hour @ 50°F LWT @ 115°F condensing temperature. Capacities may be +/5% as reserved by the compressor manufacturer. Capacity multipliers are 50°F - 1.00 ; 40°F - .80 ; 30°F - .60 ; 20°F - .40.
  • 3. Consult pump curve for exact pump performance.
  • 4. Selection of optional pumps for higher flow rates will raise the minimum recommended operating temperature when no glycol is used.
  • 5. Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
  • 6. Consult factory for 50HZ operation.
  • 7. Unit weight crated for shipment. Air-cooled units shipped in two units. Basic field assembly required for Air-cooled units.
  • Notes for Condensing Unit:
  • 1. Tons capacity at 15,000 BTU/hr/ton. Altitude Derate: .94 @ 2,000 ft, .86 @ 4000 ft, .81 @ 6000 ft.
  • 2. Vertical discharge from condenser.
  • 3. Field installation including piping connections and charging of remote air-cooled condenser by owner.
  • 4. Unit weight crated for shipment.
Get An Immediate Factory Price for this Portable Chiller
Water Chiller 40 ton Module Dual Zone Titan Series Air-Cooled
TI-40A shown with remote air-cooled condenser.

Image shown is typical. Actual unit appearance will vary according to specifications and options.
Serving Plastics and Industrial Markets since 1977
American Flag
Advantage Engineering, Inc. 525 East Stop 18 Road, Greenwood, IN 46142   Phone: 317-887-0729   Fax: 317-881-1277
Privacy Statement: we will not sell, rent or release any personal information you share with us to third party vendors.   Sitemap   
Product innovation and improvement is our constant goal. All features, specifications and pricing are subject to change without notice or liability.
Products are assembled in the United States of America.
Valid XHTML 1.0 Transitional
© 2014 ADVANTAGE ENGINEERING, INC
Advantage Engineering Provides Industry Process Cooling Equipment For Optimizing Your Process