R410A Refrigerant Piping Guide

Select either BTU/Hr or Tons/hr.

Recommended Pipe Size will appear next to Equivalent Line Lengths.

System Capacity

BTU/Hr

Tons/Hr

Discharge Line Size

Compressor to Condenser

1F° (5 PSI pressure drop maximum)

Equivalent Line Lengths (feet)
Recommended Pipe Size (inches)
25
50
75
100
150

Liquid Condensate Line

Condenser to Receiver

Ccondensate drain/vent

Equivalent Line Lengths (feet)
Recommended Pipe Size (inches)
25
50
75
100
150
 
DISCHARGE LINE SIZE COMPRESSOR TO CONDENSER 1F° (5 PSI pressure drop maximum)
LIQUID CONDENSATE LINE CONDENSER TO RECEIVER Condensate drain / vent
System Capacity BTU/Hr
System Capacity Tons/Hr
Equivalent Line Lengths (feet)
Equivalent Line Lengths (feet)
25
50
75
100
150
25
50
75
100
150

Notes:

  • Refer to DuPont Refrigerant Expert, Version 2.0 for actual velocities and pressure drops.
  • Equivalent length is actual length plus friction losses caused by fittings and accessories.
  • Line sizes are expressed in outside diameter of type “L” copper tubing.
  • Line sizes are calculated at rated full load system capacity.
  • All selections are based on a maximum of 65°F return gas entering the compressor and refrigerant condensing and liquid line temperature of 105°F.
  • Information provided for reference only. Consult your local expert for specific system recommendations.
  • Information provided by Dupont.