Relieving System Pressure When Shutting Down a G-Series Temperature Control Unit

Relieving system pressure when shutting down your mold temperature control unit with the Advantage G-Series Microprocessor Instrument follow these steps.

  1. Turn set point to 85°F and let system cool.
  2. Once cool, turn unit off.
  3. Close valves 1 & 2.
  4. Carefully open valve 3 to relieve system pressure to open drain or bucket.
  5. Caution, there will be residual pressure in the pipe between valve 2 and the cooling valve.
  6. To relieve this pressure, manually open the AVT cooling valve by following the directions in the manual vent section the manual.

Relieving System Pressure When Shutting Down a G-Series Temperature Control Unit

Download the PDF document.