Temperature Control Unit | Water Circulating | Up To 300°F
Model SRG-1645-300
Click Here for An Immediate Factory Pricing Quote For the SRG-1645-300 ▶
Pricing Is Now On Display
Product Overview
Water temperature control units are used to preheat industrial processes to the desired operating temperature by recirculating water through the process and engaging the unit’s electric immersion
heater.
After reaching the operating temperature, temperature control units can continue to add heat or become a cooling device by precisely exchanging & mixing cooling
water* with the recirculated water to maintain tight temperature control.
This temperature control unit requires a plant water supply source.
Temperature control units are portable, built on casters to easily move the unit between processes.
Temperature can for these units is 32°F to 250°F.
Price is Loading
Specifications
Model: SRG-1645-300 (1)
Heater(2)
kW : 16
Process Pump
HP : 1
GPM : 45
PSI : 30
Cooling Valve
Type : Solenoid
Size : ⅜"
Control Instrument
Type : G300 Series
Maximum Temperature : 300°F
(3)Minimum Temperature : 32°F
Construction
Electrical : Nema 1 control cabinet with branch circuit protection
Cabinetry : ABS Instrument bezel with stainless steel enclosure panels
Full Load Amperage(4)(5)
230/3/60 : 43.0
460/3/60 : 21.5
575/3/60 : 17.9
Connection Sizes
To Process : 1¼"
From Process : 1¼"
Water Supply : ½"
Drain : ½"
Dimensions
Height : 29½"
Width : 12½"
Depth : 19"
Weight(6)
Shipping : 210 lbs
Warranty
Heater & Cooling Valve : 2 Years
Control Instrument : 4 Years
Pump Seal : Lifetime
Machine : 2 Years
Specification Notes:
Since product innovation and improvement is our constant goal, all features and specifications are subject to change without notice or liability. Selection of certain optional features may change listed specifications.
Derate heater output by 25% for 208/3/60 operation.
The Sentra cannot achieve temperatures below the cooling water supply temperature and will provide warmer water to process compared to the cooling water temperature even with the cooling valve fully open. Consult Factory for more information.
Full load amps are higher than run load amps and must be used for sizing disconnects and supply wiring. Not for construction. Consult factory for power requirements of unit as configured and on selected options.
Consult factory for 50HZ operation.
Unit weight crated for shipment.
Features
NEW
Exclusive Single Piece High Efficient, High Flow Pump, Motor & Tank Assembly
Process Pump
High flow centrifugal pump and motor in one assembly
Custom designed pump casing & impeller generates high flow rate
Turbulence generated by high flow rates improves heat transfer and promotes better part quality
Horizontal orientation and internal seal area flush extends pump seal life
Integral fluid bypass reduces performance problems associated with low flow
Open drip proof motor
Electrical
DIN rail mounted UL approved finger safe electrical components
Color coded & numbered wires are easy to identify for service purposes
Control instruments are plug to plug for easy removal for service
IEC motor starter with overload, phase loss & short circuit protection